Custom Replacement Coils Request a Quote
← Back to Resources
CRC installation, operation, and maintenance guidelines. Use the checklist section to verify correct installation before startup.
Upon Delivery — Before Signing
  • Inspect crate/box for external damage before signing the freight bill
  • Look for: indentations, protruding nails, forklift marks
  • Inspect interior contents carefully for concealed damage
If Damage Is Found
  1. Accept the shipment — do not refuse delivery
  2. Note “DAMAGED” clearly on the freight bill before signing
  3. Do not move damaged equipment or discard packaging
  4. Contact CRC immediately to report the damage
  5. Wait for carrier inspection before proceeding with any repairs
  6. Contact CRC again once inspection is complete
⚠️ Accepting a damaged shipment does NOT hold you liable — as long as “DAMAGED” appears on the freight bill. Failing to note damage on the freight bill forfeits your claim.
Handling & Mounting
  • Lift by casing only — never by connections, headers, tubes, or fins
  • Install coil and piping on separate supports
  • Use backup wrenches on all connections — never torque against coil headers
  • Position tubes horizontally using a level
  • Special drain headers available if leveling the coil is not possible
Piping Connections
  • Supply water → bottom connection on the leaving-air side
  • Return water → top connection on the entering-air side
  • Run water counter-flow to air for maximum heat transfer efficiency
  • Always use thread tape or pipe compound + backup wrench on threaded connections
  • Pipe velocity: do not exceed 8 FPS (preferred range: 2–6 FPS)
  • Under 1 FPS → risk of laminar flow (poor heat transfer)
  • Over 8 FPS → risk of tube erosion
  • Recommended friction loss: ~3 feet per 100 feet of pipe
  • Support all piping independently — never let pipe weight stress coil connections
Filling & Venting
  • Open the vent at the top of the supply header before turning on water
  • Fill until a steady stream flows from the vent, then close
  • Re-vent periodically with fluid flowing to clear accumulated air pockets
Cooling Coil Specifics
  • Drain pans must extend minimum 10 inches from the coil’s leaving-air edge
  • Drain line trap depth: 2× the negative static pressure of the unit
  • For stacked coils: install intermediate drain pans with plastic tubes draining from upper units
⚠️ Minimum entering air temperature: 40°F. For applications below 40°F, use glycol or brine solutions — see Freeze Protection section.
Handling & Mounting
  • Lift by casing only — never by connections, headers, tubes, or fins
  • Non-cased coils: pitch ¼ inch per foot toward the return connection for condensate drainage
  • Steam distributing (non-freeze) coils: pitch ⅛ inch per foot of finned length toward return connection — critical for freeze protection
  • Ensure adequate piping flexibility to accommodate thermal expansion
Piping Connections
  • Steam supply → upper connection on the leaving-air side
  • Run steam counter-flow to air for maximum heat transfer
  • Do not reduce pipe size at the return connection
  • Install vacuum breakers and air vents on all applications
  • All piping must be supported independently — no pipe weight on coil connections
  • Use float and thermostatic (F&T) traps for both high- and low-pressure systems
  • Position traps minimum 12 inches below the coil return connection
  • Each individually controlled coil or coil group requires its own trap
  • Series coil arrangements: each coil or bank requires a separate trap
Control Valves
  • Modulating valves must be sized properly — DO NOT OVERSIZE
  • Steam distributing (non-freeze) coils: must use modulating control valves — on/off valves NOT permitted
Coil Type Selection Guide
Coil TypeUse WhenControl ValveMin Steam
Standard steamEntering air always ≥ 40°FOn/off OKAny pressure
Steam distributing (non-freeze)Outside air pre-heat, below-freezing entering airModulating only5 psig min
🚨 Non-freeze coils require minimum 5 psig steam supply for proper freeze protection.
Receiving & Preparation
  • Coils arrive with nitrogen holding charge — exercise caution when opening connections
  • If no nitrogen charge on arrival: contact factory before installing
  • Clean distributor connections with emery cloth if soft solder was factory-applied
Refrigerant Line Sizing & Routing
  • Use long radius fittings for all bends — minimizes pressure drop
  • Use nitrogen-charged, capped piping during installation to keep moisture out
  • Liquid line: maintain 5°F sub-cooling at the expansion valve
  • Pitch horizontal suction lines toward the compressor
  • Install traps at riser bottoms and every 15 feet on vertical risers for oil return
  • Insulate suction line completely with appropriate insulation wall thickness
  • Install pressure tap on the leaving side of the evaporator
Filter-Drier & Sight Glass
  • Install filter-drier upstream of the expansion valve
  • Maximum pressure drop through filter-drier: 2 PSI
  • Install moisture indicator/sight glass between the expansion valve and filter-drier
  • Install liquid line shutoff valve with access port near the condenser
  • TEV must be selected for proper size, capacity, and the refrigerant being used
  • Select valves with external equalizer connections
  • Mount sensing bulbs at 10 o’clock or 2 o’clock position on suction line — never on top or bottom
  • Do NOT overtighten the bulb clamp
🚨 Disassemble the TEV before brazing connections. If necessary, wrap the valve in a cool wet cloth while brazing.
Refrigerant Notes (Post Jan 1, 2026)
  • New split systems must use refrigerants with GWP <700
  • R-454B: standard for Carrier, Trane, York, Lennox ducted residential/light commercial
  • R-32: standard for Daikin, Goodman, Amana ductless mini-splits
  • R-454B and R-32 coils are NOT interchangeable with R-410A coils
  • Existing R-410A systems may be serviced and repaired indefinitely
  • Use glycol solution if operating near or below freezing temperatures
  • Minimum entering air for standard coils: 40°F — below this requires glycol or non-freeze coil design
To Winterize a Water Coil
  1. Fully drain the coil
  2. Blow out with compressed air through the return (top) connection
  3. Disconnect supply and return lines until ready to refill
⚠️ When draining coils, all water may not drain completely. Always blow out with compressed air after draining.
Glycol Freeze Points Reference
% Ethylene GlycolFreeze Point% Propylene GlycolFreeze Point
10%25°F10%26°F
20%17°F20%19°F
30%5°F30%8°F
40%-13°F40%-7°F
50%-34°F50%-29°F
  • Average coil life: ~15 years; well-maintained coils can last 25–30 years
  • Disconnect power and lock out/tag out (LOTO) before any cleaning
Cleaning Procedure
  1. Always clean from the leaving-air side — pushes debris out, not deeper into the fin pack
  2. Light dirt: vacuum or soft-bristle brush
  3. Heavy buildup: cold water with detergent, or commercial coil cleaner; pressure washer (use carefully to avoid fin damage)
  4. Rinse thoroughly after using any cleaning agent
🚨 Do NOT clean refrigerant coils with hot water or steam — causes dangerous high-pressure buildup inside tubing.
  • Avoid acidic cleaners
  • Alkaline cleaners must have pH ≤ 8.5 OR include an aluminum corrosion inhibitor
  • Always follow SDS/safety instructions and use appropriate PPE
Fin Straightening
  • Use fin combs sized to the coil’s FPI specification — wrong size will cause damage
  • Inspect fins after every shipping delivery or servicing event
  • Work carefully — fins are thin aluminum or copper and bend easily
⚠️ Steam itself is not corrosive. Steam condensate can be, if contaminated. Coils developing pin holes — especially repeated failures — signal corrosive condensate, not simply worn-out coils.
Three Primary Corrosive Agents
AgentCommon SourceAffects
OxygenAir leakage into condenserCopper alloys
Carbon Dioxide (CO₂)Air leakage or feed-water alkalinity decompositionAll copper alloys
AmmoniaContamination or pH chemical overdosingCopper alloys

Standard water treatment tests typically do NOT test for oxygen, CO₂, or ammonia — so corrosion can go undetected until pin holes appear.

Diagnosis & Solutions
  • Pin holes in tubes = direct indicator that corrosive agents have reached damaging levels
  • Test the condensate immediately after the first pin hole — do not simply replace the coil
  • Solution 1: Replace with stainless steel tubes and headers
  • Solution 2: Cleanse the system of corrosive agents (addresses the root cause)
🚨 Thicker tube walls do NOT solve corrosion. It is the material’s corrosion resistance that matters, not thickness. Replacing with the same-material coil without fixing water chemistry = rapid re-failure.
Coil TypeMax PressureNotes
Steam coils150 psig saturated steam
Fluid coils (standard)300 psig250°F max for single-phase fluids
Fluid coils (elliptical ½″ × 0.016″)250 psig
Fluid coils (elliptical ½″ × 0.025″)450 psig
Evaporator coils750 psigR-410A rated
Condenser coils750 psigR-410A rated
ℹ️ All coils pressure tested at 550 psig using dry nitrogen, submerged under water, with dual-operator verification before shipping.
General — All Coil Types
Water Coils
Steam Coils
Refrigerant / DX Coils
  • All installations must comply with local codes and standards — non-compliance may void manufacturer warranty
  • Do not substitute a water coil for a steam coil — completely different construction, pressure ratings, and tube wall requirements
  • Refrigerant coils for R-454B or R-32 are NOT interchangeable with R-410A coils
  • Do not clean coils with hot water or steam
  • Do not use acidic cleaners or alkaline cleaners above pH 8.5 without aluminum corrosion inhibitor
  • Always lock out/tag out power before cleaning or servicing any coil
📞 For questions or coil replacements, contact CRC directly.
Answer a few questions about what you're seeing and get targeted troubleshooting steps. No login required.